Autoreclosing of 110–500 kV mixed transmission lines using a distance method to determine the damaged section

D.Yu. Vikharev, E.A. Vorobyeva, A.Yu. Murzin, N.A. Rodin

Vestnik IGEU, 2025 issue 4, pp. 19—27

Download PDF

Abstract in English: 

Background. To identify damage on a cable section of mixed 110–500 kV power transmission lines, a number of methods are currently being used. Their effectiveness is achieved due to the use of additional equipment and the organization of communication channels. There are methods that make it possible to identify damage of the cable without using additional devices. However, they have a significant disadvantage due to the inability to determine short circuit near the transition point from the overhead section to the cable section. Thus, the important task is to develop an effective method to determine the damaged section of a mixed transmission line without the use of additional equipment.

Materials and methods. Methods of mathematical modeling of electrical circuits have been used. The implementation of the distance method to determine the damaged section and evaluate the effectiveness of its application has been carried out in the PSCAD. The results of the research have been processed by the MathCAD computer-aided design system and the MATLAB software package.

Results. A distance method is proposed to determine the damaged section of a mixed transmission line based on the emergency mode parameters when the cable is located at any of its sections. The authors have analyzed the influence of the grounding location of the cable shield on the effectiveness of the autoreclosing of a mixed power transmission line. The authors have studied the effect of the mutual angle between the electromotive forces of the systems on the sides of the mixed transmission line on the effectiveness of the distance method to determine the damaged section.

Conclusions. The developed method to determine the damaged section makes it possible to increase the efficiency of autoreclosing of mixed transmission lines. The limitations of the applicability of the method are related to the use of short cables located at a distance from the beginning and end of the power transmission line. To increase the efficiency of the developed method for lines with short cable section, the use of special high-precision algorithms to determine signal parameters is required. 

References in English: 

1. Ovchinnikov, V.V. Avtomaticheskoe povtornoe vklyuchenie [Autoreclosing]. Moscow: Energoatomizdat, 1986. 96 p.

2. Dmitriev, M.V. Kabel'nye linii vysokogo napryazheniya [High-voltage cable lines]. Saint-Petersburg: POLITEKh-PRESS, 2021. 688 p.

3. Goryachikh, A.D. Avtomaticheskoe povtornoe vklyuchenie kabel'no-vozdushnykh liniy s primeneniem elektronnykh opticheskikh transformatorov toka. Pilotnyy proekt na PS 220 kV «Gertsevo». AO «OEK» [Autoreclosing of cable-overhead lines using electronic optical current transformers. Pilot project at the 220 kV Herzevo substation. JSC UEK]. Elektroenergiya. Peredacha i raspredelenie, 2019, no. 1(52), pp. 116–118.

4. Dmitriev, M.V. Avtomaticheskoe povtornoe vklyuchenie na vozdushno-kabel'nykh liniyakh elektroperedachi 110–500 kV [Autoreclosing on overhead cable power transmission lines 110–500 kV]. Elektroenergiya. Peredacha i raspredelenie, 2015, no. 1(28), pp. 68–73.

5. Alekseev, V.G., Arutyunov, S.A., Balashov, S.V., Erokhin, E.Yu., Il'in, M.D., Mitrofanov, N.N., Nudel'man, G.S., Sdobin, A.V., Smekalov, V.V., Shapeev, A.A. Selektivnoe avtomaticheskoe povtornoe vklyuchenie kabel'no-vozdushnykh liniy elektroperedachi napryazheniem 110 kV i vyshe [Selective autoreclosing of cable-overhead power transmission lines with a voltage of 110 kV and higher]. Elektroenergiya. Peredacha i raspredelenie, 2018, no. 3(48), pp. 94–101.

6. Zhivykh, A.A., Kukharchuk, A.V. Avtomaticheskoe povtornoe vklyuchenie s funktsiey kontrolya sostoyaniya linii elektroperedachi [Autoreclosing with the function of monitoring the state of the power line]. Materialy Vserossiyskoy nauchno-tekhnicheskoy konferentsii Avtomatizirovannye sistemy upravleniya i informatsionnye tekhnologii. V 2 t., Perm', 09–11 iyunya 2020 g. [Proceedings of All-Russian scientific and technical conference, in 2 vols., Perm, June 9–11, 2020]. Perm': Permskiy natsional'nyy issledovatel'skiy politekhnicheskiy universitet, 2020, pp. 164–168.

7. Davletshina, A.M. Organizatsiya releynoy zashchity i avtomatiki liniy elektroperedachi s kabel'nym uchastkom v nachale linii [Organization of relay protection and automation of power transmission lines with a cable section at the beginning of the line]. Materialy Mezhdunarodnoy molodezhnoy nauchnoy konferentsii «Energetika i tsifrovaya transformatsiya» (Tinchurinskie chteniya – 2021). V 3 t., Kazan', 28–30 aprelya 2021 g. [Proceedings of international youth scientific conference Tinchurin Readings – 2021 “Energy and Digital Transformation”. In 3 vols., Kazan, April 28–30, 2021]. Kazan': OOO PK «Astor i Ya», 2021, pp. 328–331.

8. Goldsborough, S.L., Smith, R.M. A new distance ground relay. Transactions of the American Institute of Electrical Engineers, 1936, vol. 55, no. 6, pp. 697–703.

9. Arzhannikov, E.A. Distantsionnyy printsip v releynoy zashchite i avtomatike liniy pri zamykaniyakh na zemlyu [Distance principle in relay protection and automation of lines during ground faults]. Moscow: Energoatomizdat, 1985. 176 p.

Key words in Russian: 
автоматическое повторное включение, дистанционный принцип определения места повреждения, кабельно-воздушная линия электропередачи, измерительный орган сопротивления от однофазных коротких замыканий на землю
Key words in English: 
autoreclosing, fault location distance method, mixed transmission line, distance measuring device for single-phase ground faults