Study of the electromagnetic compensator of the third harmonic current in the neutral of a power transformer

Yu.I. Khanin, T.A. Kuznetsova, A.P. Panchishkin

Vestnik IGEU, 2026 issue 3, pp. 52—58

Download PDF

Abstract in English: 

Background. The study is relevant due to the increase in the number of non-linear electrical receivers, such as computers, televisions, LED lamps and other devices, in household electrical networks in rural areas. The increase in the number of such devices leads to distortion of the consumed current and voltage waveforms, causing deviations from the ideal sinusoidal shape. The widespread use of power transformers with “star-star- with neutral” winding configurations, which have high zero-sequence impedance increase the negative impact of harmonic current components. The primary objective of the research is to study an electromagnetic device aimed at compensating third harmonic currents in the neutral conductor of power transformers in rural electrical systems.

Materials and methods. The electromagnetic compensator of the third harmonic current for the neutral of a power transformer under study is implemented in the form of a circuit that includes six current transformers installed in the network phases, a three-phase half-wave rectifier, a filter choke and an additional current transformer in the neutral. The technical solution using six transformers and a rectifier allows for compensation of currents that are multiples of the third harmonic, which is especially effective in networks with a “star-star with neutral” winding configuration and high sensitivity to zero-sequence harmonics.

Results. To evaluate the efficiency of the device, measurements have been conducted on low-voltage buses of thirteen 10/0,4 kV transformer substations supplying the household sector in the Volgograd region. A power quality analyzer has been employed to record current, voltage, power, and harmonic composition parameters at a one-minute resolution over a 24-hour cycle. The findings have confirmed that the third current harmonic is the dominant factor in parasitic power losses within residential grid power transformers, contributing an average of 67,2 % of the total losses caused by higher-order harmonics. Field tests in four-wire networks of rural 10/0,4 kV substations have demonstrated the high efficiency of the electromagnetic compensator. After installation, the neutral third harmonic amplitude has decreased by 64,4 %, resulting in a 9,95 % reduction in total electricity losses.

Conclusions. Thus, targeted suppression of the third harmonic not only enhances network stability but also ensures significant resource savings, particularly under conditions of growing non-linear loads.

References in English: 

1. Kostinskiy, S.S., Mokhov, V.A., Kruglova, T.N., Shaikhutdinov, D.V., Vlasov, A.S. Agent-based approach for analysis of electricity distribution technological processes in power systems. IOP Conference Series: Materials Science and Engineering, Volgograd, 20–21 November 2018. Volgograd: Institute of Physics Publishing, 2019, p. 012080. DOI: 10.1088/1757-899X/483/1/012080.

2. Kostinskiy, S., Troitskiy, A. Impact study of non-sinusoidal load parameters on real-power losses in 3-phase double-wound power transformers: Method of constant coefficients. Journal of Engineering and Applied Sciences, 2017, vol. 12, no. 20, pp. 5058–5068. DOI: 10.3923/jeasci.2017.5058.5068.

3. Yudaev, I.V., Rud, E.V., Yundin, M.A., Ponomarenko, T.Z., Isupova, A.M. Analysis of the harmonic composition of current in the zero-working wire at the input of the load node with the prevailing non-linear power consumers. Archives of Electrical Engineering, 2021, vol. 70, no. 2, pp. 463–473. DOI: 10.24425/aee.2021.136996.

4. Khanin, Yu.I., Ivanova, O.A., Aksenov, M.P. Optimizatsiya vybora parametrov fil′trokompensiruyushchikh ustroystv na primere sel′skokhozyaystvennogo mashinostroitel′nogo zavoda [Optimization of the selection of parameters of filter-compensating devices using the example of an agricultural engineering plant]. Vestnik IGEU, 2025, issue 4, pp. 50–56. DOI: 10.17588/2072-2672.2025.4.050-0564.

5. Yudaev, I.V., Rud, E.V., Ponomarenko, T.Z., Yundin, M.A., Isupova, A.M. The harmonic composition of current in zero-working wire with non-linear load. IIUM Engineering Journal, 2021, vol. 22, no. 1, pp. 191–200. DOI: 10.31436/IIUMEJ.V22I1.1569.

6. Hanin, Y.I., Rodionova, O.V., Panchishkin, A.P., Zaichkina, M.A., Shakhbazova, Y.E. On the efficiency of power transformers with “star-zig-zag with zero” winding connection scheme in rural electricity networks supplying household consumers. Journal of Physics: Conference Series: 2, Volgograd, Virtual, 06–07 May 2021. Volgograd, Virtual, 2021, p. 012004. DOI: 10.1088/1742-6596/2060/1/012004.

7. Hanin, Y.I., Pelih, A.E., Nikolaeva, S.I., Ivanova, O.A. The optimization of the filter compensating devices parameters choice at the enterprises of agro-industrial complex. IOP Conference Series: Earth and Environmental Science: 3, Volgograd, Virtual, 10–11 December 2020. Volgograd, Virtual, 2021, p. 012015. DOI: 10.1088/1755-1315/786/1/012015.

8. Yundin, M.A., Shabanov, N.I., Khanin, Yu.I. O koeffitsiente nebalansa naibolee znachimykh vysshikh garmonik tokov v sel′skikh kommunal′no-bytovykh setyakh 0,38 kV [On the unbalance factor of the most significant higher harmonics of currents in rural public utility networks of 0,38 kV]. Vestnik APK Stavropolya, 2014, no. 2(14), pp. 102–104.

9. Yundin, M.A., Khanin Yu.I.  Dopolnitel'nye poteri elektroenergii v silovykh transformatorakh 10/0,4 kV [Additional power losses in 10/0,4 kV power transformers]. Politematicheskiy setevoy elektronnyy nauchnyy zhurnal Kubanskogo gosudarstvennogo agrarnogo universiteta, 2014, no. 101, pp. 74–84.

10. Yundin, M., Ponomarenko, T., Yundin, K. Analiz sverkhnormativnykh poter′ moshchnosti v silovykh transformatorakh 10/0,4 kV, imeyushchikh nagruzku s preobladaniem nelineynykh potrebiteley [Analysis of excess power losses in 10/0,4 kV power transformers with a load dominated by non-linear consumers]. Elektroenergiya. Peredacha i raspredelenie, 2021, no. S1(20), pp. 6–12.

11. Yundin, M.A., Kobzistyy, O.V., Rud′, E.V. Otsenka vliyaniya urovney nesimmetrii i vysshikh garmonik na tok v nulevom rabochem provodnike seti 0,38 kV [Assessment of the influence of asymmetry levels and higher harmonics on the current in the neutral working conductor of a 0,38 kV network]. Vestnik agrarnoy nauki Dona, 2021, no. 3(55), pp. 33–38.

12. Yundin, M.A., Zharikov, D.T., Ponomarenko, T.Z. O vliyanii nesimmetrii i nesinusoidal'nosti tokov na poteri elektroenergii v silovom transformatore [On the influence of asymmetry and non-sinusoidality of currents on energy losses in a power transformer]. Agrotekhnika i energoobespechenie, 2021, no. 4(33), pp. 114–118.

Key words in Russian: 
силовой трансформатор, электромагнитный компенсатор, несинусоидальность токов, третья гармоника тока, компенсация гармонических составляющих тока
Key words in English: 
power transformer, electromagnetic compensator, non-sinusoidal currents, third harmonic of current, compensation of harmonic components of current
The DOI index: 
10.17588/2072-2672.2026.3.052-058
Downloads count: 
11