Русская версия English version

Development of a device to prevent ferroresonance phenomena in 6–10 kV isolated-neutral networks

A.N. Antonov, V.D. Lebedev

Vestnik IGEU, 2026 issue 4, pp. 49—57

Download PDF

Abstract in English: 

Background. Occurrence of ferroresonance is one of the dangerous mode characteristics of isolated-neutral networks. Various manufacturers have developed numerous methods to prevent this type of process, but the choice of a specific solution in each individual case remains a pressing issue due to the inherent drawbacks of each solution. Consequently, there is a need to develop a device that is considered as a universal and affordable measure to prevent ferroresonance phenomena in isolated-neutral networks.

Materials and methods. The study has been conducted using the physical modeling method based on a test-bed for modeling the operation a 6–10 kV network.

Results. The advantages and disadvantages of existing solutions to prevent the development of ferroresonances in isolated-neutral networks have been investigated. The device to prevent ferroresonance phenomena in 6–10 kV networks developed under order of NTZ Volkhov LLC, has been studied. Experimental oscillograms have been obtained confirming the effectiveness of the proposed solution.

Conclusions. Proposed device makes it possible to effectively prevent flow of ferroresonance in 6–10 kV isolated-neutral networks. In the proposed solution, a number of drawbacks characteristic of currently existing analogues have been eliminated.

References in English: 

1. Valverde, V., Buigues, G., Mazón, A.J., Zamora, I., Albizu, I. Ferroresonant Configurations in Power Systems. Renew. Energy Power Qual. J., 2012, vol. 10, no. 4, pp. 474–479. DOI: 10.24084/repqj10.351.

2. Araujo, A.E.A., Soudack, A.C., Marti, J.R. Ferroresonance in power systems: chaotic behaviour. IEE Proceedings-c, May 1993, vol. 140, pp. 237–240. DOI: 10.1049/ip-c.1993.0035.

3. Valverde, V., Mazón, A.J., Zamora, I., Buigues, G. Ferroresonance in voltage transformers: Analysis and simulations. Renew. Energy Power Qual. J., 2007, vol. 1, no. 5, pp. 465–471. DOI: 10.24084/repqj05.317.

4. Piasecki, W., Florkowski, M., Fulczyk, M., Mahonen, P., Nowak, W. Mitigating Ferroresonance in Voltage Transformers in Ungrounded MV Networks. IEEE Transactions on Power Delivery, October 2007, vol. 22, no. 4, pp. 2362–2369. DOI: 10.1109/TPWRD.2007.905383.

5. CIGRE WG C4.307 Technical Brochure 569 – Resonance and Ferroresonance in Power Networks. February 2014.

6. Zikherman, M.Kh. Transformatory napryazheniya dlya setey 6–10 kV. Prichiny povrezhdaemosti [Voltage transformers for 6–10 kV networks. The causes of damageability]. Novosti elektrotekhniki, 2003, no. 1(25).

7. Borisenko, L.S., Panasyuk, D.I., Strelyaev, P.I. Predotvrashchenie povrezhdeniy transformatorov napryazheniya kontrolya izolyatsii 35 kV pri zamykaniyakh na zemlyu [Prevention of damage to 35 kV insulation control voltage transformers in case of earth faults]. Energetik, 1983, no. 9, pp. 21–23.

8. Dudarev, L.E., Voloshek, I.V., Levkovskiy, A.I. Chislennyy analiz ferrorezonansnykh protsessov v setyakh s izolirovannoy neytral'yu [Numerical analysis of ferroresonance processes in isolated-neutral networks]. Elektricheskie stantsii, 1991, vol. 1, pp. 66–71.

9. Petrov, O.A. Smeshchenie neytrali pri pofaznykh otklyucheniyakh i obryvakh faz v kompensirovannoy seti [Neutral displacement during phase disconnections and phase failures in compensated networks]. Elektricheskie stantsii, 1972, no. 9, pp. 57–61.

10. Kadomskaya, K.P., Laptev, O.I. Issledovanie effektivnosti antirezonansnykh transformatorov napryazheniya tipa NAMI v setyakh 6–35 kV s izolirovannoy neytral'yu [Efficiency study of anti-resonance voltage transformers of NAMI type in 6–35 kV systems with isolated neutral]. Nauchnyy vestnik NGTU, 2006, no. 4(25), pp.167–175.

11. Matveev, D.A. O tekhnicheskikh trebovaniyakh k antirezonansnym transformatoram napryazheniya i ikh standartizatsii [About technical requirements for anti-resonance voltage transformers and their standardization]. Elektroenergiya. Peredacha i raspredelenie, 2023, no. 1(76), pp. 114–115.

12. STO 56947007-29.240.10.191–2014. Metodicheskie ukazaniya po zashchite ot rezonansnykh povysheniy napryazheniya v elektroustanovkakh 6–750 kV [Procedural Guidelines on Resonance Overvoltage Protection in 6–750 kV Electrical Installations]. OAO FSK EES, Moscow, 2014.

13. Kosarev, B.A. Ferrorezonansnye perenapryazheniya v elektroustanovkakh 6–220 kV: teoriya i rezul'taty eksperimental'nykh issledovaniy [Ferroresonance overvoltages in electrical installations 6–220 kV: theory and results of experimental studies]. Elektrotekhnicheskie i informatsionnye kompleksy i sistemy, 2022, no. 3–4, pp. 45–55. DOI: 10.17122/1999-5458-2022-18-3-4-45-55.

14. Tarko, R., Nowak, W., Gajdzica, J., Czapp, S. Analysis of Ferroresonance Mitigation Effectiveness in Auxiliary Power Systems of High-Voltage Substations. Energies, 2024, vol. 17, no. 10, p. 2423.

15. Martínez, R., Mañana, M., Rodríguez, J.I., Álvarez, M., Mínguez, R., Arroyo, A., Bayona, E., Azcondo, F.J., Pigazo, A., Cuartas, F. Ferroresonance phenomena in medium-voltage isolated neutral grids: a case study. IET Renewable Power Generation, 2019, vol. 13, issue 1, pp. 209–214. DOI: 10.1049/iet-rpg.2018.5231.

16. Zikherman, M.Kh. Antirezonansnye transformatory napryazheniya. Tekhnicheskie trebovaniya i metody ispytaniy [Anti-resonance voltage transformers. Technical requirements and test methods]. Novosti elektrotekhniki, 2011, no. 2(68).

17. Laptev, O.I. Ob effektivnosti primeneniya sovremennykh antirezonansnykh transformatorov napryazheniya v setyakh 6–35 kV [On the efficiency of using modern anti-resonance voltage transformers in 6–35 kV networks]. Materialy vserossiyskoy konferentsii «Ogranichenie perenapryazheniy. Rezhimy zazemleniya neytrali. Elektrooborudovanie setey 6–35 kV», Novosibirsk, 16–18 sentyabrya 2008 goda [Proceedings of All Russian conference “Surge Limitation. Neutral Grounding Modes. Electrical Equipment of 6–35 kV Networks”, Novosibirsk, September 16–18, 2008]. Novosibirsk: Izdatel′stvo Novosibirskogo gosudarstvennogo tekhnicheskogo universiteta, 2008.

18. Burchevskiy, V.A., Vladimirov, L.V., Oshchepkov, V.A., Surikov, V.I. Obzor rezhimov zazemleniya neytrali v elektricheskikh setyakh 6–35 kV [Overview of neutral grounding modes in electrical networks 6–35 kV]. ONV, 2009, no. 1(77), pp. 122–126.

19. Fishman, V.S. Transformatory napryazheniya. Sposoby ustraneniya ferrorezonansnykh yavleniy [Voltage transformers. Ways to eliminate ferroresonance phenomena]. Novosti elektrotekhniki, 2010, no. 6(66).

20. Antonov, A.N., Lebedev, V.D. Development of the Experimental Set-Up for Testing MV Voltage Transformers Resistance to Ferroresonance. 2025 International Conference on Industrial Engineering, Applications and Manufacturing (ICIEAM). Sochi, 2025, pp. 821–825. DOI: 10.1109/ICIEAM65163.2025.11028571.

21. Antonov, A.N., Lebedev, V.D. Issledovanie ferrorezonansnykh yavleniy v elektromagnitnykh transformatorakh napryazheniya setey 6–10 kV pri vozdeystvii dugovykh peremezhayushchikhsya odnofaznykh zamykaniy na zemlyu [Study of ferroresonance phenomena in 6–10 kV electromagnetic voltage transformers when exposed to intermittent single-phase earth faults]. Vestnik IGEU, 2025, issue 6, pp. 51–57. DOI: 10.17588/2072-2672.2025.6.051-057.

22. Venikov, V.A. Teoriya podobiya i modelirovaniya (primenitel′no k zadacham elektroenergetiki) [Similarity and Modeling Theory (Applied to Electric Power Engineering Tasks)]. Moscow: Vysshaya shkola, 1976. 479 p.

23. NTZ Volkhov LLC. Ustroystvo zashchity transformatora ot ferrorezonansnykh yavleniy [Device for transformer protection against ferroresonance phenomena]. Patent RF, no. 2026106829, 2026.

Key words in Russian: 
феррорезонанс, сети с изолированной нейтралью, антирезонансное устройство, однофазное замыкание на землю, моделирование сети с изолированной нейтралью, трансформатор напряжения, физическое моделирование
Key words in English: 
ferroresonance, isolated-neutral networks, antiresonance device, single-phase ground fault, isolated neutral network modeling, voltage transformer, physical modeling
The DOI index: 
10.17588/2072-2672.2026.4.049-057
Downloads count: 